The Parameters for Aeons Labs Smart Switch 6 are not well documented in the manual, below you’ll find the complete parameter list.
A basic parameter setup to get feedback when the switch is manually operated and to get power readings would be:
Parameter (dec) |
Description | Value |
80 (1d) | Status feedback to controller when manually operated |
1 (Fibaro Homecenter 2/Lite) 2 (Vera Edge) |
101 (4d) | Auto report power readings to group 1 (Controller) | 15 |
And the complete parameter setup is:
Parameter Number (dec) |
Description | Default value | Size |
3 | Current Overload Protection. Load will be closed when the Current overrun (US: 15.5A, other country: 16.2A) and the time more than 2 minutes (0=disabled, 1=enabled). |
0 | 1 |
20 | Configure the output load status after re‐power on (0=last status, 1=always on, 2=always off) |
0 | 1 |
33 | Set the RGB LED color value for testing. Value1: Reserved Value2: Red value Value3: Green value Value4: Blue value |
– | 4 |
80 | Enable to send notifications to associated devices (Group 1) when the state of Switch’s load changed (0=nothing, 1=hail CC, 2=basic CC report). |
0 | 1 |
81 | Configure the state of LED when it is in 3 modes below: 0= The LED will follow the status (on/off) of its load (Energy mode). 1= When the state of Switch’s load changed, The LED will follow the status (on/off) of its load, but the red LED will turn off after 5 seconds if there is no any switch action (momentary indicate mode). 2= Night light mode. |
0 | 1 |
83 | Configure the RGB value when it is in Night light mode. Value1: Red color value Value2: Green color value Value3: Blue color value |
Value1=0xDD Value2=0xA0 Value3=0xDD |
3 |
84 | Configure the brightness level of LED indication (0%‐100%) | 50 | 1 |
90 | Enables/disables parameter 91 and 92 below (1=enabled, 0=disabled). |
1 | 1 |
91 | The value here represents minimum change in wattage (in terms of wattage) for a REPORT to be sent (Valid values 0‐ 60000). |
25 (w) | 2 |
92 | The value here represents minimum change in wattage percent (in terms of percentage) for a REPORT to be sent (Valid values 0‐100). |
5 (%) | 1 |
101 | Which reports need to send in Report group 1 (See flags in table below). |
0x00 00 00 04 | 4 |
102 | Which reports need to send in Report group 2 (See flags in table below). |
0x00 00 00 08 | 4 |
103 | Which reports need to send in Report group 3 (See flags in table below). |
0 | 4 |
111 | The time interval of sending Report group 1 (Valid values 0x01‐0x7FFFFFFF). |
0x00 00 02 58 | 4 |
112 | The time interval of sending Report group 2 (Valid values 0x01‐0x7FFFFFFF). |
0x00 00 02 58 | 4 |
113 | The time interval of sending Report group 3 (Valid values 0x01‐0x7FFFFFFF). |
0x00 00 02 58 | 4 |
200 | Partner ID (0= Aeon Labs Standard Product, 1= others). |
0 | 1 |
252 | Enable/disable Configuration Locked (0 =disable, 1 = enable). |
0 | 1 |
254 | Device Tag | 0 | 2 |
255 | Reset configuration set up to default setting. | N/A | 1 |
Configuration Values for parameter 101-103
7 | 6 | 5 | 4 | 3 | 2 | 1 | 0 | |
configuration Value 1(MSB |
Reserved | |||||||
configuration Value 2 | Reserved | |||||||
configuration Value 3 | Reserved | |||||||
configuration value 4 (LSB) | Reserved | Reserved | Reserved | Reserved | Auto send Meter REPORT (for kWh) at the group time interval |
Auto send Meter REPOR T (for watt) at the group time interval |
Auto send Meter REPORT (for current) at the group time interval |
Auto send Meter REPOR T (for voltage at the group time interval |